Rated voltage U0/U: 0,6/1 kV.
Test voltage: 3,5 kV (5 minutes).
Maximum conductor temperature for normal operation is 70C.
Maximum conductor temperature for short-circuit (5s maximum duration) is:
140C with Nominal area larger than 300mm2.
160C with Nominal area up to and include 300mm2.
Wires are subjected to fire at 9500C for 3 hours.
Wires pass BS 6387 Cat. CWZ.
The fire resistant wires have a significant reduced tendency to propagate fire.
The wires must self-extinguish after removing the fire source.
Against Cable
The fireproof cable is suitable for use in public buildings, backup power systems, emergency systems, fire alarm systems, fire fighting water systems, smoke alarms and smoke extraction systems, emergency exit light systems. …